CR8 – 32/3 to 2 x 16/3

Home  |  Products   |  Power Distribution Hire   |  POWER DISTRIBUTION – 32 AMP  |  CR8 – 32/3 to 2 x 16/3
Unit Specification Supply Connection Load Connection
Unit Standard BS EN 61439-3 Inlet Standard BS EN 60309-1+2 Outlets Standard BS EN 60309-1+2
Approx Dim: WxDxH 400x350x340 Amperage (A) 32 1ph Voltage 400
Enclosure (IP) IP44 Voltage 400
Impact (IK) IK>06 Connection 3ph+N+E
Appliance inlet
Unit Max. Amps 32A
Voltage (V) 400V
Frequency Hz 50Hz Supply Isolation Connectivity
Continuous Load 70% BS EN 60898 32C 2X 16A Sockets 3ph+N+E
TYPE MCB
Protection Devices
Device Voltage Rating Type & Amperage Character – mA kA – Short Circuit Rating Device Standard(s)
MCB 400 16 30 6 BS EN 60898